Service visit 2026-10-12 09:10 UTC
Service visit
- Arrived
- 2026-10-12 09:10 UTC
- Departed
- 2026-10-12 10:20 UTC
- Findings
- Residual current device tripping repeatedly in wet weather. Earth leakage found at connector 2 socket.
- Actions taken
- Replaced Type 2 socket outlet on connector 2, reset RCD, monitored for 30 minutes.
- Warranty claim
- –
Made for work order (ForWorkOrder) 1
- WO-2026-01389 · P3 · Verified
Part fittings used (UsedInServiceVisit) 1
- 2026-10-12 10:00 UTC · Fault · 1 pcs